Installation

3 Installation

3.1 Pre-Installation

3.1.1 Planning the Installation Site

NOTICE
Plan the installation site of the frequency converter
before commencing the installation. Neglecting this may
result in extra work during and after installation.
Select the best possible operation site by considering
the following (see details on the following pages and
the respective Design Guides):
Ambient operating temperature
Installation method
How to cool the unit
Position of the frequency converter
Cable routing
Ensure that the power source supplies the correct
voltage and necessary current.
Ensure that the motor current rating is within the
maximum current from the frequency converter.
If the frequency converter is without built-in
fuses, ensure that the external fuses are rated
correctly.
Voltage [V] Altitude restrictions
380-690
At altitudes above 2000 m, contact Danfoss
regarding PELV
Table 3.1 Installation at High Altitudes

3.1.2 General Considerations

Wire access
Ensure that proper cable access is present including
necessary bending allowance. As the IP00/IP20 enclosure is
open to the bottom, cables must be fixed to the back
panel of the enclosure where the frequency converter is
mounted, i.e. by using cable clamps.
CAUTION
All cable lugs/shoes must mount within the width of the
terminal bus bar.
Space
Ensure proper space above and below the frequency
converter to allow airflow and cable access. In addition
space in front of the unit must be considered to enable
opening of the panel door, see Illustration 3.1 to
Illustration 3.3.
MG16J202
Operating Instructions
Illustration 3.1 Front Clearance of IP21/IP54 Rated Enclosure
Types D1h, D5h, and D6h
Illustration 3.2 Front Clearance of IP21/IP54 Rated Enclosure
Types D2h, D7h, and D8h
Illustration 3.3 Front Clearance of IP21/IP54 Rated Enclosure
Type E1
Danfoss A/S © Rev. 05/2014 All rights reserved.
298
[11.7]
404
[15.9]
105
395
[15.6]
523
[20.6]
105
579
(22.8)
748
≤105,0°
(29.5)
3
3