5.3 Control Terminal Programming
Examples
Control terminals can be programmed.
Each terminal has specified functions it is capable
of performing
Parameters associated with the terminal enable
the function
For proper frequency converter functioning, the
control terminals must be
Wired properly
Programmed for the intended function
Receiving a signal
See Table 2.4 for control terminal parameter number and
default setting. (Default setting can change based on the
selection in 0-03 Regional Settings.)
The following example shows accessing Terminal 18 to see
the default setting.
1.
Press [Main Menu] twice, scroll to parameter
group 5-** Digital In/Out and press [OK].
14.6%
Main Menu
2-** Brakes
3-** Reference / Ramps
4-** Limits / Warnings
5-** Digital In/Out
Illustration 5.11
2.
Scroll to parameter group 5-1* Digital Inputs and
press [OK].
14.7%
Digital In/Out
5-0* Digital I/O mode
5-1* Digital Inputs
5-4* Relays
5-5* Pulse Input
Illustration 5.12
3.
Scroll to 5-10 Terminal 18 Digital Input. Press [OK]
to access function choices. The default setting
Start is shown.
®
VLT
AQUA Drive
Operating Instructions
5.4 International/North American Default
Setting 0-03 Regional Settings to International or North
America changes the default settings for some parameters.
The next table lists those parameters that are effected.
0-03 Regional
Settings
0-71 Date Format
0-72 Time Format
1-20 Motor Power
[kW]
0.00A
1(1)
1-21 Motor Power
[HP]
1-22 Motor Voltage 230V/400V/575V
1-23 Motor
Frequency
3-03 Maximum
Reference
3-04 Reference
Function
4-13 Motor Speed
High Limit [RPM]
See Note 3
0.00A
1(1)
4-14 Motor Speed
High Limit [Hz]
5-**
See Note 4
4-19 Max Output
Frequency
4-53 Warning Speed
High
5-12 Terminal 27
Digital Input
5-40 Function Relay Alarm
6-15 Terminal 53
High Ref./Feedb.
Value
6-50 Terminal 42
Output
14-20 Reset Mode
®
MG.20.M8.02 - VLT
is a registered Danfoss trademark
14.7%
Digital Inputs
5-10 Terminal 18 Digital
Input
[8]] Start
Illustration 5.13
Parameter Settings
Parameter
International
Default Parameter
Value
International
YYYY-MM-DD
24h
See Note 1
See Note 2
20 - 1000Hz
50Hz
Sum
1500RPM
50Hz
1.0 - 1000.0Hz
1500RPM
Coast inverse
50
100
Automatic reset x 10 Infinite auto reset
0.00A
1(1)
5-1*
5
North American
Default Parameter
Value
North America
MM/DD/YYYY
12h
See Note 1
See Note 2
208V/460V/575V
60Hz
60Hz
External/Preset
1800RPM
60Hz
120Hz
1800RPM
External interlock
No alarm
60
Speed 4-20mA
35
5