5.3 Control Terminal Programming
Examples
Control terminals can be programmed.
•
Each terminal has specified functions it is capable
of performing
•
Parameters associated with the terminal enable
the function
•
For proper frequency converter functioning, the
control terminals must be
Wired properly
Programmed for the intended function
Receiving a signal
See Table 2.4 for control terminal parameter number and
default setting. (Default setting can change based on the
selection in 0-03 Regional Settings.)
The following example shows accessing Terminal 18 to see
the default setting.
1.
Press [Main Menu] twice, scroll to parameter
group 5-** Digital In/Out and press [OK].
14.6%
Main Menu
2-** Brakes
3-** Reference / Ramps
4-** Limits / Warnings
5-** Digital In/Out
Illustration 5.11
2.
Scroll to parameter group 5-1* Digital Inputs and
press [OK].
14.7%
Digital In/Out
5-0* Digital I/O mode
5-1* Digital Inputs
5-4* Relays
5-5* Pulse Input
Illustration 5.12
3.
Scroll to 5-10 Terminal 18 Digital Input. Press [OK]
to access function choices. The default setting
Start is shown.
®
VLT
AQUA Drive
Operating Instructions
5.4 International/North American Default
Setting 0-03 Regional Settings to International or North
America changes the default settings for some parameters.
The next table lists those parameters that are effected.
0-03 Regional
Settings
0-71 Date Format
0-72 Time Format
1-20 Motor Power
[kW]
0.00A
1(1)
1-21 Motor Power
[HP]
1-22 Motor Voltage 230V/400V/575V
1-23 Motor
Frequency
3-03 Maximum
Reference
3-04 Reference
Function
4-13 Motor Speed
High Limit [RPM]
See Note 3
0.00A
1(1)
4-14 Motor Speed
High Limit [Hz]
5-**
See Note 4
4-19 Max Output
Frequency
4-53 Warning Speed
High
5-12 Terminal 27
Digital Input
5-40 Function Relay Alarm
6-15 Terminal 53
High Ref./Feedb.
Value
6-50 Terminal 42
Output
14-20 Reset Mode
®
MG.20.M8.02 - VLT
is a registered Danfoss trademark
14.7%
Digital Inputs
5-10 Terminal 18 Digital
Input
[8]] Start
Illustration 5.13
Parameter Settings
Parameter
International
Default Parameter
Value
International
YYYY-MM-DD
24h
See Note 1
See Note 2
20 - 1000Hz
50Hz
Sum
1500RPM
50Hz
1.0 - 1000.0Hz
1500RPM
Coast inverse
50
100
Automatic reset x 10 Infinite auto reset
0.00A
1(1)
5-1*
5
North American
Default Parameter
Value
North America
MM/DD/YYYY
12h
See Note 1
See Note 2
208V/460V/575V
60Hz
60Hz
External/Preset
1800RPM
60Hz
120Hz
1800RPM
External interlock
No alarm
60
Speed 4-20mA
35
5