Warnings and Alarms
No.
Description
49
Speed limit
50
AMA calibration failed
51
AMA check U
and I
nom
nom
52
AMA low I
nom
53
AMA motor too big
54
AMA motor too small
55
AMA Parameter out of range
56
AMA interrupted by user
57
AMA timeout
58
AMA internal fault
59
Current limit
60
External Interlock
62
Output Frequency at Maximum Limit
64
Voltage Limit
65
Control board overtemperature
66
Heat sink Temperature Low
67
Option Configuration has Changed
68
1)
Safe Stop
69
Pwr.card temp
70
Illegal FC configuration
77
Reduced Power Mode
79
Illegal PS config
80
Drive Initialized to Default Value
91
Analog input 54 wrong settings
92
NoFlow
93
Dry Pump
94
End of Curve
95
Broken Belt
96
Start Delayed
97
Stop Delayed
98
Clock Fault
99
Locked rotor
104
Mixing Fan Fault
250
New spare parts
251
New Type Code
Table 9.1 Alarm/Warning Code List
(X) Dependent on parameter
1)
Cannot be Auto reset via 14-20 Reset Mode

9.5 Fault Messages

The following warning/alarm information defines each
warning/alarm condition, provides the probable cause for
the condition, and details a remedy or troubleshooting
procedure.
WARNING 1, 10 Volts low
The control card voltage is below 10 V from terminal 50.
Remove some of the load from terminal 50, as the 10 V
supply is overloaded. Max. 15 mA or minimum 590 Ω.
This condition can be caused by a short in a connected
potentiometer or improper wiring of the potentiometer.
MG16J202
Operating Instructions
Warning
Alarm/Trip
X
(X)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
(X)
(X)
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Troubleshooting
WARNING/ALARM 2, Live zero error
This warning or alarm only appears if programmed by the
user in 6-01 Live Zero Timeout Function. The signal on one
of the analog inputs is less than 50% of the minimum
value programmed for that input. Broken wiring or faulty
device sending the signal can cause this condition.
Danfoss A/S © Rev. 05/2014 All rights reserved.
Alarm/Trip lock
Parameter reference
1-86 Trip Speed Low [RPM]
X
5-19 Terminal 37 Digital Input
X
X
X
X
22-2* No-Flow Detection
22-2* No-Flow Detection
22-5* End of Curve
22-6* Broken Belt Detection
22-7* Short Cycle Protection
22-7* Short Cycle Protection
0-7* Clock Settings
14-53 Fan Monitor
X
X
Remove the wiring from terminal 50. If the
warning clears, the problem is with the customer
wiring. If the warning does not clear, replace the
control card.