Introduction

1.6 Internal Controller Functions

Illustration 1.5 is a block diagram of the frequency
converter's internal components.
Illustration 1.5 Frequency Converter Block Diagram
MG16J202
Operating Instructions
Area
1
2
3
4
5
6
7
8
Table 1.2 Legend to Illustration 1.5
Danfoss A/S © Rev. 05/2014 All rights reserved.
Title
3-phase AC mains supply to the
Mains input
frequency converter
The rectifier bridge converts the
AC input to DC current to
Rectifier
supply inverter power.
Intermediate DC-bus circuit
DC-bus
handles the DC current.
Filter the intermediate DC circuit
voltage.
Prove line transient protection.
Reduce RMS current.
DC reactors
Raise the power factor reflected
back to the line.
Reduce harmonics on the AC
input.
Stores the DC power.
Capacitor bank
Provides ride-through protection
for short power losses.
Converts the DC into a
controlled PWM AC waveform
Inverter
for a controlled variable output
to the motor.
Regulated 3-phase output
Output to motor
power to the motor
Input power, internal
processing, output, and motor
current are monitored to
provide efficient operation and
control.
Control circuitry
User interface and external
commands are monitored and
performed.
Status output and control can
be provided.