Danfoss VLT FC 103 Operating Instructions Manual page 28

Refrigeration drive 75-630 kw
Hide thumbs Also See for VLT FC 103:
Table of Contents

Advertisement

Installation
3-phase
power
input
3
3
DC bus
+10 V DC
0/-10 V DC-
+10 V DC
0/4-20 mA
0/-10 V DC -
+10 V DC
0/4-20 mA
Illustration 3.23 Interconnect Diagram
A=Analog, D=Digital
*Terminal 37 (optional) is used for Safe Torque Off. For Safe Torque Off installation instructions, refer to the VLT
Converters - Safe Torque Off Operating Instructions.
**Do not connect cable screen.
26
Operating Instructions
91 (L1)
92 (L2)
93 (L3)
95
PE
88 (-)
89 (+)
10 V DC
15 mA 130/200 mA
50 (+10 V OUT)
+
S201
53 (A IN)
ON=0/4-20 mA
S202
OFF=0/-10 V DC -
+10 V DC
54 (A IN)
55 (COM A IN)
12 (+24 V OUT)
13 (+24 V OUT)
P 5-00
18 (D IN)
19 (D IN)
20 (COM D IN)
27
(D IN/OUT)
24 V
0 V
*
29
(D IN/OUT)
24 V
0 V
32 (D IN)
33 (D IN)
*
37 (D IN)
Danfoss A/S © Rev. 05/2014 All rights reserved.
Switch Mode
Power Supply
24 V DC
-
+
-
24 V (NPN)
0 V (PNP)
24 V (NPN)
(COM A OUT) 39
0 V (PNP)
24 V (NPN)
S801
0 V (PNP)
ON=Terminated
OFF=Open
5V
24 V (NPN)
0 V (PNP)
S801
RS-485
(N RS-485) 69
Interface
24 V (NPN)
0 V (PNP)
(P RS-485) 68
24 V (NPN)
(COM RS-485) 61
0 V (PNP)
(U) 96
(V) 97
(W) 98
(PE) 99
Motor
(R+) 82
Brake
resistor
(R-) 81
relay1
03
240 V AC, 2 A
02
01
relay2
*
06
240 V AC, 2 A
05
400 V AC, 2 A
04
Analog Output
0/4-20 mA
(A OUT) 42
0 V
RS-485
**
®
Frequency
: Chassis
: Ground
: PE
: Ground 1
: Ground 2
MG16J202

Advertisement

Table of Contents
loading