Installation
Transfer impedance, Z
mOhm/m
10
10
3
3
10
10
10
1
10
10
10
0,01
0,1
a
Aluminium-clad with copper wire
b
Twisted copper wire or armoured steel wire cable
c
Single-layer braided copper wire with varying percentage
screen coverage (this is the typical Danfoss reference
cable).
d
Double-layer braided copper wire
e
Twin layer of braided copper wire with a magnetic,
screened/armoured intermediate layer
f
Cable that runs in copper tube or steel tube
g
Lead cable with 1.1 mm wall thickness
Illustration 3.54 Cable Screening Performance
3.5.3 Grounding of Screened Control
Cables
Correct screening
The preferred method in most cases is to secure control
and serial communication cables with screening clamps
provided at both ends to ensure best possible high
frequency cable contact. If the ground potential between
the frequency converter and the PLC is different, electric
noise may occur that disturbs the entire system. Solve this
problem by fitting an equalizing cable next to the control
cable. Minimum cable cross section: 16 mm
50
Operating Instructions
a
t
b
c
d
e
f
1
10
100 MHz
g
2
.
Danfoss A/S © Rev. 05/2014 All rights reserved.
PLC
PE
PE
1
2
1
Min. 16 mm
2
2
Equalizing cable
Illustration 3.55 Correct Screening
50/60 Hz ground loops
With very long control cables, ground loops may occur. To
eliminate ground loops, connect one end of the screen-to-
ground with a 100 nF capacitor (keeping leads short).
PLC
PE
100nF
Illustration 3.56 Avoiding Ground Loops
Avoid EMC noise on serial communication
This terminal is connected to ground via an internal RC
link. Use twisted-pair cables to reduce interference
between conductors. The recommended method is shown
below:
FC
69
68
61
PE
PE
2
1
2
Min. 16 mm
2
Equalizing cable
Illustration 3.57 Avoiding EMC Noise
Alternatively, the connection to terminal 61 can be
omitted:
FC
69
68
PE
PE
1
2
1
2
Min. 16 mm
2
Equalizing cable
Illustration 3.58 Screening without Using Terminal 61
FC
PE
<10 mm
PE
FC
PE
<10 mm
FC
69
68
61
PE
<10 mm
PE
1
FC
68
69
PE
<10 mm
PE
MG16J202