Connection Examples; Start/Stop; Pulse Start/Stop - Danfoss VLT AutomationDrive FC 302 Operating Instructions Manual

90–1200 kw
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

How to Install
NOTICE
When changing the function of S201, S202 or S801 be
careful not to use force for the switch over. It is
recommended to remove the LCP fixture (cradle) when
operating the switches. The switches must not be
3
3
operated with power on the frequency converter.
Illustration 3.79

3.6 Connection Examples

3.6.1 Start/Stop

Terminal 18 = 5-10 Terminal 18 Digital Input [8] Start
Terminal 27 = 5-12 Terminal 27 Digital Input [0] No
operation (Default coast inverse)
Terminal 37 = Safe Torque Off
Speed
Start/Stop
[18]
Illustration 3.80

3.6.2 Pulse Start/Stop

Terminal 18 = 5-10 Terminal 18 Digital Input [9] Latched
start
Terminal 27= 5-12 Terminal 27 Digital Input [6] Stop inverse
Terminal 37 = Safe Torque Off
76
®
VLT
Automation Drive FC 300 Operating Instructions
12 13 18
19
27
29
32
33 20
37
Start/Stop
Safe Stop
12
13
Start
Speed
Start (18)
Start (27)
Illustration 3.81
3.6.3 Speed Up/Down
Terminals 29/32 = Speed up/down
Terminal 18 = 5-10 Terminal 18 Digital Input [9]
Start (default)
Terminal 27 = 5-12 Terminal 27 Digital Input [19]
Freeze reference
Terminal 29 = 5-13 Terminal 29 Digital Input [21]
Speed up
Terminal 32 = 5-14 Terminal 32 Digital Input [22]
Speed down
NOTICE
Terminal 29 only in FC x02 (x=series type).
Illustration 3.82 Speed Up/Down
MG33U402 - Rev. 2013-12-16
18
19
27
29
32
33
20
37
Stop inverse
Safe Stop
12
+24V
18
Par. 5-10
27
Par. 5-12
29
Par. 5-13
32
Par. 5-14
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents