How to Install
UL compliance
Enclosure
FC 300 power
Size
A1
3
3
A2
A3
B3
B4
C3
C4
A4
A5
B1
B2
C1
C2
Table 3.26 200-240 V, Frame Sizes A, B, and C
58
VLT
Recommended
fuse size
[kW]
0.25-1.5
gG-10
0.25-2.2
gG-10 (0.25-1.5)
gG-16 (2.2)
3.0-3.7
gG-16 (3)
gG-20 (3.7)
5.5
gG-25
7.5-15
gG-32 (7.5)
gG-50 (11)
gG-63 (15)
18.5-22
gG-80 (18.5)
aR-125 (22)
30-37
aR-160 (30)
aR-200 (37)
0.25-2.2
gG-10 (0.25-1.5)
gG-16 (2.2)
0.25-3.7
gG-10 (0.25-1.5)
gG-16 (2.2-3)
gG-20 (3.7)
5.5-7.5
gG-25 (5.5)
gG-32 (7.5)
11
gG-50
15-22
gG-63 (15)
gG-80 (18.5)
gG-100 (22)
30-37
aR-160 (30)
aR-200 (37)
®
Automation Drive FC 300 Operating Instructions
Recommended
max. fuse
gG-25
gG-25
gG-32
gG-63
gG-125
gG-150 (18.5)
aR-160 (22)
aR-200 (30)
aR-250 (37)
gG-32
gG-32
gG-80
gG-100
gG-160 (15-18.5)
aR-160 (22)
aR-200 (30)
aR-250 (37)
MG33U402 - Rev. 2013-12-16
Recommended circuit
Max trip level
breaker
Moeller
PKZM0-16
PKZM0-25
PKZM0-25
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
NZMB2-A200
NZMB2-A250
[A]
16
25
25
50
100
150
250
25
25
63
100
160
250