Installation Of D Or E Loadshare Option; F Enclosure Panel Options; Enclsoure Type F Options - Danfoss VLT AutomationDrive FC 302 Operating Instructions Manual

90–1200 kw
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

How to Install
NOTICE
Where RFI filters are available, there are 2 different type of RFI filters depending on the input plate combination and
the RFI filters interchangeable. Field installable kits in certain cases are the same for all voltages.
380-480 V
380-500 V
D1
All D1 power sizes
D2
All D2 power sizes
E1
FC 102/ FC 202: 315 kW
FC 302: 250 kW
FC 102/ FC 202: 355 -
450 kW
FC 302: 315 - 400 kW
Table 3.11 Fuses
525 - 690 V
D1
FC 102/ FC 202: 45-90
kW
FC 302: 37-75 kW
FC 102/ FC 202:
110-160 kW
FC 302: 90-132 kW
D2
All D2power sizes
E1
FC 102/ FC 202:
450-500 kW
FC 302: 355-400 kW
FC 102/ FC 202:
560-630 kW
FC 302: 500-560 kW
Table 3.12
NOTICE
For further information, see the Instruction Installation of
Field Installable Kits for VLT Drives
3.3.12 Installation of D or E Loadshare
Option
The loadshare option can be installed on frame sizes D1,
D2, D3, D4, E1 and E2.
NOTICE
See the Loadshare Terminal Kit Instructions, 175R5637 (D
frames) or 177R1114 (E frames), for further information.
Ordering information
Frame size D1/D3: 176F8456
Frame size D2/D4: 176F8455
Frame size E1/E2: 176F1843
®
VLT
Automation Drive FC 300 Operating Instructions
Fuses
Disconnect Fuses
176F8442
176F8450
176F8443
176F8441
176F0253
176F0255
176F0254
176F0256
Fuses
Disconnect Fuses
175L8829
175L8828
175L8442
175L8445
175L8827
175L8826
176F0253
176F0255
176F0254
176F0258

3.4 F Enclosure Panel Options

3.4.1 Enclsoure Type F Options

Space Heaters and Thermostat
Mounted on the cabinet interior of enclosure type F
frequency converters, space heaters controlled via
automatic thermostat help control humidity inside the
enclosure, extending the lifetime of frequency converter
components in damp environments. The thermostat
default settings turn on the heaters at 10 °C (50 °F) and
turn them off at 15.6 °C (60 °F).
Cabinet Light with Power Outlet
A light mounted on the cabinet interior of enclosure type
F frequency converters increase visibility during servicing
and maintenance. The housing the light includes a power
outlet for temporarily powering tools or other devices,
available in two voltages:
MG33U402 - Rev. 2013-12-16
RFI
RFI Fuses
176F8444
176F8448
176F8445
176F8449
176F0257
176F0258
176F0257
176F0259
RFI
RFI Fuses
175L8777
NA
175L8777
NA
175L8825
NA
NA
NA
NA
NA
230 V, 50 Hz, 2.5 A, CE/ENEC
120 V, 60 Hz, 5 A, UL/cUL
RFI Disconnect
3
3
Fuses
176F8446
176F8447
176F0260
176F0262
RFI Disconnect
Fuses
NA
NA
NA
NA
NA
41

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents