Very long control cables and analog signals may in rare
cases and depending on installation result in 50/60 Hz
ground loops due to noise from mains supply cables.
If this occurs, it may be necessary to break the screen or
insert a 100 nF capacitor between screen and chassis.
Connect the digital and analog inputs and outputs
separately to the frequency converter common inputs
(terminal 20, 55, 39) to avoid ground currents from both
groups to affect other groups. For example, switching on
the digital input may disturb the analog input signal.
Input polarity of control terminals
PNP (Source)
Digital input wiring
12
13
18
19
27
Illustration 3.76
NPN (Sink)
Digital input wiring
12
13
18
19
27
Illustration 3.77
®
VLT
Automation Drive FC 300 Operating Instructions
29
32
33
20
37
29
32
33
20
37
MG33U402 - Rev. 2013-12-16
NOTICE
Control cables must be screened/armoured.
Illustration 3.78
Connect the wires as described in the product related
Operating Instructions. Remember to connect the shields in
a proper way to ensure optimum electrical immunity.

3.5.24 Switches S201, S202, and S801

Switches S201 (A53) and S202 (A54) are used to select a
current (0-20 mA) or a voltage (-10 to +10 V) configuration
of the analog input terminals 53 and 54.
Switch S801 (BUS TER.) can be used to enable termination
on the RS-485 port (terminals 68 and 69).
See Illustration 3.74.
Default setting:
S201 (A53) = OFF (voltage input)
S202 (A54) = OFF (voltage input)
S801 (Bus termination) = OFF