Product Certifications - Emerson Rosemount 3051S Manual Supplement

Hide thumbs Also See for Rosemount 3051S:
Table of Contents

Advertisement

Rosemount 3051S High Pressure
2017
Section 9
Rev 2.6
9.1
Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that the design meets the basic
electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory
(NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA).
9.2
European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most
recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount.
9.3
Installing Equipment in North America
The US National Electrical Code
marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable
for the area classification, gas, and temperature class. This information is clearly defined in the respective
codes.
9.4
USA
E5
I5
IE
52

Product Certifications

Explosionproof, Dust Ignition-proof
Certificate: 143113
Standards: FM Class 3600 - 2011, FM Class 3615 - 2006, FM Class 3810 - 2005, UL 1203 5th Ed., UL
50E 1st Ed., UL 61010-1 (3rd Edition)
Markings: XP CL I, DIV 1, GP B, C, D; T5; DIP CL II, DIV 1, GP E, F, G; CL III; T5(–50 °C
Seal Not Required; Type 4X
US Intrinsically Safe; Nonincendive
Certificate: 1143113
Standards: FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004, FM Class 3810 -
2005, UL 50E 1st Ed., UL 61010-1 (3rd Edition)
Markings: IS CL I,II,III, DIV 1, GP A, B, C, D, E, F, G, T4; Class 1, Zone 0 AEx ia IIC
T4(–50 °C
T
a ≤
B, C, D, T5, T
= 70 °C; Rosemount drawing 03251-1006; Type 4X
a
US FISCO Intrinsically Safe
Certificate: 1143113
Standards: FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3810 - 2005, UL 50E 1st Ed., UL
61010-1 (3rd Edition)
Markings: IS CL I, DIV 1, GP A, B, C, D, T4(–50 °C
Rosemount drawing 03251-1006; Type 4X
®
(NEC) and the Canadian Electrical Code (CEC) permit the use of Division
+70 °C) [HART]; T4(–50 °C
T
a ≤
+60 °C) [Fieldbus]; NI CL 1, DIV 2, GP A,
T
+60 °C); Class 1, Zone 0 AEx ia IIC T4;
a ≤
Rosemount 3051S High Pressure
Manual Supplement
00809-0100-4851, Rev AA
T
a ≤
+85 °C);