Product Certifications - Emerson Rosemount 248 Quick Start Manual

Rail mount temperature transmitter
Hide thumbs Also See for Rosemount 248:

Advertisement

January 2024
5 

Product certifications

Rev: 1.1
5.1 
European Directive information
A copy of the EU Declaration of Conformity can be found at the
end of the Quick Start Guide. The most recent revision of the EU
Declaration of Conformity can be found at Emerson.com/Rosemount.
5.2 
Ordinary location certification
As standard, the transmitter has been examined and tested to
determine that the design meets the basic electrical, mechanical,
and fire protection requirements by a Nationally Recognized Test
Laboratory (NRTL) as accredited by the Federal Occupational Safety
and Health Administration (OSHA).
5.3 
Installing equipment in North America
The US National Electrical Code
Code (CEC) permit the use of Division marked equipment in Zones
and Zone marked equipment in Divisions. The markings must be
suitable for the area classification, gas, and temperature class. This
information is clearly defined in the respective codes.
5.4 
USA
5.4.1  I5 USA Intrinsically Safe (IS) and Division 2/Zone 2
Certificate
Standards
Markings
Quick Start Guide
80072530
UL Std No 913 Ed. 8, UL 60079-0 Ed. 5, UL 60079-11 Ed. 6,
UL 60079-15 Ed. 4, UL 61010-1 Ed. 3
Class I, Division 1, Groups A, B, C, D
Class I, Zone 0: AEx ia IIC T6...T4
Class I, Zone 1: AEx ib [ia] IIC T6...T4
Class I, Division 2, Groups A, B, C, D
Class I, Zone 2: AEx nA IIC T6...T4
Class I, Zone 2: AEx nA [ic] IIC T6...T4
Note
When installed per Control Drawing 00248-8000.
(NEC) and the Canadian Electrical
®
Quick Start Guide
17