U4 Or Uf Transmission Error (Between Indoor Unit And Outdoor Unit) - Daikin R71FUV1 Service Manual

Skyair series service diagnosis
Table of Contents

Advertisement

Troubleshooting by Remote Controller
U4
3.92
(Between Indoor Unit and
Outdoor Unit)
Remote Controller Display
U4
UF
or
Applicable Models
R(Y)-FU
Method of Error Detection
Micro-computer checks if transmission between indoor
and outdoor units is normal.
Error Decision Conditions
When transmission is not carried out normally for a
certain amount of time
Supposed Causes
Wiring indoor-outdoor transmission wire is incorrect.
Defective indoor unit PCB
Defective outdoor unit PCB
External factor (Noise, etc.)
UF
or
Transmission Error
Si20-701_B