E6 Compressor Overcurrent - Daikin R71FUV1 Service Manual

Skyair series service diagnosis
Table of Contents

Advertisement

Troubleshooting by Remote Controller
E6
3.33
Remote Controller Display
E6
Applicable Model
R(Y)-LU, RR-M
Method of Error Detection
The input current value is detected with a current sensor.
Error Decision Conditions
When the compressor input current exceeds the
specified input current value.
∗ Refer to "Approximate Input current value" on
following page.
Possible Causes
High pressure increased too high
Voltage drop
Stop valve is not opened
Defective compressor (compressor lock)
Compressor Overcurrent