Troubleshooting for FTX, FVXS Series
5.6
Signal Transmission Error (Between Indoor Unit and
Outdoor Unit)
U4
Error Code
Method of Error
The signal transmission data received from the outdoor unit is checked whether it is normal.
Detection
Error Decision
The data sent from the outdoor unit cannot be received normally, or the content of the data is
Conditions
abnormal.
Supposed
 Power supply voltage not as specified
Causes
 Reduction of power supply voltage
 Wiring error
 Breaking of the connection wires between the indoor and outdoor units (wire No. 3)
 Defective outdoor unit PCB
 Short circuit inside the fan motor winding
 Defective indoor unit PCB
 Disturbed power supply waveform
135