E3 High Pressure Abnormality (Hps) - Daikin R71FUV1 Service Manual

Skyair series service diagnosis
Table of Contents

Advertisement

Si20-701_B
E3
3.26
(HPS)
Remote Controller Display
E3
Applicable Models
RZQ-K/H, RZQ(S)-B/C, RZR-KU/HU
Method of Error Detection
The protection device circuit checks continuity in the high
pressure switch.
Error Decision Conditions
When the high pressure switch is actuated
Supposed Causes
Defective high pressure switch
Disconnection in high pressure switch harness
Defective connection of high pressure switch
connector
Clogged indoor unit suction filter (in heating)
Dirty outdoor unit heat exchanger
Defective outdoor unit fan
Refrigerant overcharge
Stop valve is not opened