Daikin R71FUV1 Service Manual page 470

Skyair series service diagnosis
Table of Contents

Advertisement

Troubleshooting by Remote Controller
For discharge pipe thermistor
T°C
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
kΩ
3257.371
2429.222
1827.883
1387.099
1061.098
817.9329
635.0831
496.5712
391.0070
309.9511
247.2696
198.4674
160.2244
130.0697
106.1517
87.0725
71.7703
59.4735
49.5180
Si20-701_B
T°C
65
41.4168
70
34.7923
75
29.3499
80
24.8586
85
21.1360
90
18.0377
95
15.4487
100
13.2768
105
11.4395
110
9.8902
115
8.5788
120
7.4650
125
6.5156
130
5.7038
135
5.0073
140
4.4080
145
3.8907
150
3.4429
3SA48006 (AD87A001J)
kΩ
463