Signal Transmission Error (Between Indoor Unit And Outdoor Unit) - Daikin Super Multi NX FFQ25B8V1B Service Manual

E-series, f-series, g-series
Hide thumbs Also See for Super Multi NX FFQ25B8V1B:
Table of Contents

Advertisement

Troubleshooting for RA Indoor Unit - F(C)TXG, FTXS, ATXS, FVXS, FLK(X)S, FDK(X)S Series
5.6
Signal Transmission Error (between Indoor Unit and
Outdoor Unit)
U4
Remote
Controller
Display
Method of
The data received from the outdoor unit in indoor unit-outdoor unit signal transmission is
checked whether it is normal.
Malfunction
Detection
Malfunction
The data sent from the outdoor unit cannot be received normally, or the content of the data is
abnormal.
Decision
Conditions
Supposed
Causes
316
Defective outdoor unit PCB
Defective indoor unit PCB
Wiring error
Disturbed power supply waveform
Breaking of the connection wires between the indoor and outdoor units (wire No. 3)
SiBE121021_C
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Super multi nx fvxs35fv1bSuper multi nx ffq35b8v1bSuper multi nx fbq35c7vebSuper multi nx ftxs35g2v1bSuper multi nx fvxs50fv1bSuper multi nx ffq50b8v1b ... Show all

Table of Contents