F6 Refrigerant Overcharged - Daikin R71FUV1 Service Manual

Skyair series service diagnosis
Table of Contents

Advertisement

Si20-701_B
F6
3.40
Remote Controller Display
F6
Applicable Models
CMSQ
Method of Error Detection
Excessive charging of refrigerant is detected by using the
outdoor air temperature, heat exchanger deicer
temperature and liquid pipe temperature during check
operation.
Error Decision Conditions
When the amount of refrigerant, which is calculated by
using the outdoor air temperature, heat exchanging
deicer temperature and liquid pipe temperature during
check operation, exceeds the criteria.
Supposed Causes
Refrigerant overcharge
Disconnection of outdoor air thermistor
Disconnection of heat exchanger deicer thermistor
Defective liquid pipe thermistor
222
Refrigerant Overcharged
Troubleshooting by Remote Controller