Daikin R71FUV1 Service Manual page 148

Skyair series service diagnosis
Table of Contents

Advertisement

Troubleshooting by Remote Controller
Remote Controller Display
E1
Applicable Models
CMSQ
Method of Error Detection
Check data from E²PROM
Error Decision Conditions
When data could not be correctly received from the
E²PROM
E²PROM : Type of nonvolatile memory. Maintains
memory contents even when the power supply is turned
OFF.
Supposed Causes
Defective outdoor unit PCB
Troubleshooting
Caution
Turn OFF the power
once and turn ON again.
Return to
normal?
NO
Check if
inside/outside
relay wires of outdoor
unit main PCB is
disconnected.
NO
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.
YES
YES
Si20-701_B
External factor
other than error
(for example,
noise etc.).
Connect the
inside/outside
relay wires
correctly.
Replace the
outdoor unit main
PCB.
141