Ua Improper Combination Of Indoor And Outdoor Units, Indoor Units And Remote Controller - Daikin R71FUV1 Service Manual

Skyair series service diagnosis
Table of Contents

Advertisement

Troubleshooting by Remote Controller
UA
3.99
Indoor and Outdoor Units,
Indoor Units and Remote
Controller
Remote Controller Display
UA
Applicable Models
FMCQ, FMDQ-A7/B7
CMSQ
Method of Error Detection
A difference occurs in data by the type of refrigerant
between indoor and outdoor units.
The number of indoor units is out of the allowable range.
Error Decision Conditions
The error decision is made as soon as either of the
abnormalities aforementioned is detected.
Supposed Causes
Excess of connected indoor units
Defective outdoor unit PCB (A1P)
Mis-matching of the refrigerant type of indoor and
outdoor unit.
Setting of outdoor unit PCB was not conducted after
replacing to a spare PCB.
Improper Combination of
Si20-701_B
427