E4 Low Pressure System Abnormality - Daikin R71FUV1 Service Manual

Skyair series service diagnosis
Table of Contents

Advertisement

Troubleshooting by Remote Controller
E4
3.31
Abnormality
Remote Controller Display
E4
Applicable Models
RZQ-C
Method of Error Detection
Detect errors by the low pressure sensor.
Error Decision Conditions
When the detection pressure is the following value
Actuating pressure: 0.07MPa
Supposed Causes
Defective low pressure switch
Disconnection of the wire harness of the low pressure
switch
Defective connection of the connector of the low
pressure switch
The refrigerant piping circuit abnormality
The stop valve is not opened
Defective outdoor unit main PCB
Refrigerant shortage
Low Pressure System
Si20-701_B
173