Troubleshooting By Remote Controller; Procedure Of Self-Diagnosis By Remote Controller - Daikin R71FUV1 Service Manual

Skyair series service diagnosis
Table of Contents

Advertisement

Si20-701_B
3. Troubleshooting by Remote
Controller
3.1 Procedure of Self-diagnosis
by Remote Controller
3.1.1 Wired Remote Controller —
BRC1C61/BRC1D61
If operation stops due to error, the remote controller's
operation LED blinks, and error code is displayed. (Even
if stop operation is carried out, error contents are
displayed when the inspection mode is entered.) The
error code enables you to tell what kind of error caused
operation to stop.
Display of
indoor unit for
which an error
has been
detected
Inspection
display
INSPECTION/
TEST button
Note:
1. Pressing the INSPECTION/TEST button will blink the
check indication.
2. While in service mode, holding down the ON/OFF
button for a period of 5 seconds or more will clear the
error history indication shown above. In this case, on
the codes display, the error code will blink twice and
then change to "00" (= Normal), the Unit No. will
change to "0", and the operation mode will
automatically switch from service mode to normal
mode (displaying the set temperature).
54

Troubleshooting by Remote Controller

Operation LED
ON/OFF button
Error code