Mounting and installation
2

Wiring sequence for IP55

2.4.2
2.5
10
Siemens AG
PM230
Cable type
Shielded
Unshielded
Filter B
Shielded
Shielded
Unshielded
1. You may only use copper wire of class 1, 75°C (for compliance with the UL in
frame sizes A to C).
2. Ensure that the appropriate circuit breakers or fuses with the specified current
rating are connected between the power supply and the drive.

Cable cross-sections

Frame size
Power
kW
FSA
0.37...1.5
2.2...3
FSB
4
5.5...7.5
FSC
11
15...18.5
FSD
22.0...30
FSE
37
45
FSF
55
75...90
Cable cross-section of the grounding conductors
The material of the protective grounding conductor must be the same as the
material of the power cable. If this is not the case, the specific resistance of the
protective grounding conductor must not be higher than the specific resistance of
the power cables. The relevant diameter of the power cables is the diameter of the
line supply cable, and not the diameter of the motor cables.
In the case of power cables up to 35 mm
section of at least 10 mm² (16 mm² Al).
It is always advisable to use a 16mm
For power cables with a diameter of more than 35 mm
conductor must have at least half of the size of the cross-section of the power
cable.
Wiring sequence for IP55
The requirements and actions for wiring the Power Module correctly are described
below.
EMC category
C3
None
C1 (conducted only)
C2
None
Cable cross-section
mm
AWG
2
1.0 ... 2.5
18...14
1.5...2.5
16...14
2.5...6.0
14...10
4.0...6.0
12...10
6.0 ... 16
10 ... 5
10 ... 16
7 ... 5
10...35
5...2
25...50
3...2
35...50
2...4/0
70...120
2/0...4/0
95...120
3/0...4/0
, the ground cable must have a cross-
2
Cu equipotential bonding conductor at least.
2
2
Max. cable length
50 m (164 ft)
100 m (330 ft)
25 m (80 ft) with IP54
50 m (164 ft) with IP20
50 m (164 ft)
100 m (330 ft)
Tightening torques
Nm
lbf in
0.5
4.4
0.5
4.4
0.6
5.3
0.6
5.3
1.5
13.3
1.5
13.3
6
53
6
53
6
53
13
115
13
115
, the protective grounding
CM2G5111en
2014-05-16