ioLogik E1200 Series

ioLogik E1210

Inputs and Outputs
Digital Inputs: 16 channels
Isolation: 3k VDC or 2k Vrms
Digital Input
Sensor Type: Wet Contact (NPN or PNP), Dry Contact
I/O Mode: DI or Event Counter
Dry Contact:
• On: short to GND
• Off: open
Wet Contact (DI to COM):
• On: 10 to 30 VDC
• Off: 0 to 3 VDC
Common Type: 8 points per COM
Counter Frequency: 250 Hz
Digital Filtering Time Interval: Software configurable
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 110 mA @ 24 VDC
MTBF
(mean time between failures)
Time: 671,345 hrs
Standard: Telcordia SR332

ioLogik E1211

Inputs and Outputs
Digital Outputs: 16 channels
Isolation: 3k VDC or 2k Vrms
Digital Output
Type: Sink
I/O Mode: DO or Pulse Output
Pulse Output Frequency: 500 Hz
Over-Voltage Protection: 45 VDC
Over-Current Protection: 2.6 A (4 channels @ 650 mA)
Over-Temperature Shutdown: 175°C (typical), 150°C (min.)
Current Rating: 200 mA per channel
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 200 mA @ 24 VDC
MTBF
(mean time between failures)
Time: 923,027 hrs
Standard: Telcordia SR332
1-5