I/O Settings

DI Channels

The status of each DI (digital input) channel appears on the DI Channel Settings page.
You can also configure each channel's digital input mode and parameters by clicking on the channel. DI
channels can operate in DI mode or Event Counter mode.
Activate Event Counter mode by selecting the Counter Start field and configure the Counter Trigger by
selecting Lo to Hi, Hi to Lo, or Both from the dropdown menu. When the Counter Start field is not selected,
you can still activate the counter by using Modbus commands.
NOTE
Confirm that the Counter Filter is not set to 0; otherwise, the counter will never be activated.
Power On Settings: You may configure DI channels in Event Counter mode whether or not counting begins
when powering up.
Safe Status Settings: For DI channels in Event Counter mode, you can configure whether or not counting
starts or continues when Safe Status has been activated. When the network connection is lost, as specified in
the Host Connection Watchdog, the ioLogik E1200 will start or stop the counter according to the channel's Safe
Status settings.