ioLogik E1200 Series
ioLogik E1260
Inputs and Outputs
RTDs: 6 channels
Isolation: 3k VDC or 2k Vrms
RTD
Sensor Type:
• PT50, PT100, PT200, PT500 (-200 to 850°C)
• PT1000 (-200 to 350°C)
• Resistance of 310, 620, 1250, and 2200 ohms
Input Connection: 2- or 3-wire
Sampling Rate:
• All channels: 12 samples/sec
• Per channel: 2 samples/sec
• Only one channel enabled: 12 samples/sec
Resolution: 0.1°C or 0.1 ohm
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Input Impedance: 625 kilo-ohms
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 110 mA @ 24 VDC
MTBF
(mean time between failures)
Time: 660,260 hrs.
Standard: Telcordia SR332
1-11