Iologik E1262 - Moxa Technologies ioLogik E1210 User Manual

Iologik e1200 series
Hide thumbs Also See for ioLogik E1210:
Table of Contents

Advertisement

ioLogik E1200 Series

ioLogik E1262

Inputs and Outputs
Thermocouples: 8 channels
Isolation: 3k VDC or 2k Vrms
Thermocouple
Sensor Type: J (0 to 750°C), K (-200 to 1250°C), T (-200 to 350°C),
E (-200 to 900°C), R (-50 to 1600°C), S (-50 to 1760°C), B (600 to 1700°C), N (-200 to 1300°C)
Millivolt Type:
• Mode: ±78.126 mV, ±39.062 mV, ±19.532 mV
• Fault and over-voltage protection:
-35 to +35 VDC (power off)
-25 to +30 VDC (power on)
Sampling Rate:
• All channels: 12 samples/sec
• Per channel: 1.5 samples/sec
• Only one channel enabled: 12 samples/sec
Resolution: 16 bits
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Input Impedance: 10 mega-ohms
Power Requirements
Input Voltage: 12 to 36 VDC
Input Current: 118 mA @ 24 VDC
MTBF
(mean time between failures)
Time: 631,418 hrs.
Standard: Telcordia SR332