5 SETTINGS
The difference in angle can be used as the
inserting a resistance equal to the
ing the angle at this setting.
SH STATOR GND OC PICKUP: This setting specifies the backup overcurrent pickup level based on sub-harmonic cur-
rent. This protection can be used in addition to the sub-harmonic injection based 100% ground fault and fundamental
phasor over voltage based 95% ground fault protection. One per-unit value of current is the sensitive ground CT sec-
ondary rating setting, which is always 5 A since the CT used is rated for 5 A secondary.
SH STATOR GND OC DELAY: This setting specifies a time delay for sub-harmonic current based backup over current
protection. Thermal capabilities of the loading resistor or neutral grounding transformer should be considered while
setting this delay.
SH STATOR GND Vsupv: The 20 Hz source can be monitored using this voltage supervision. This setting in pu pro-
vides the voltage level below which if the sub-harmonic voltage phasor magnitude remains for a period of 10 seconds,
the
SH STATOR GND TRB OP
ondary voltage setting or the equivalent primary voltage if used in primary. A typical setting of 1 V is suggested. How-
ever, when the neutral grounding transformer's load resistance is less than 0.5 ohms, the use of voltage supervision is
not recommended.
SH STATOR GND Isupv: The 20 Hz source can be monitored using this current supervision. This setting in per-unit
values provides the current level below which if the sub-harmonic current phasor magnitude remains for a period of 10
seconds, the
SH STATOR GND TRB OP
ondary rating setting or the primary rating if used in primary. A typical setting of 0.002 pu (=10 mA in secondary) is rec-
ommended with the provided 5 A secondary CT.
The logic for the sub-harmonic stator ground fault feature is shown below.
Figure 5–116: SUB-HARMONIC STATOR GROUND FAULT LOGIC
GE Multilin
SH CT ANGLE COMPEN
SH STATOR GND STG2 PICKUP
operand will be asserted. One per-unit value of voltage is the auxiliary VT nominal sec-
operand will be asserted. One per-unit current is the sensitive ground CT sec-
G60 Generator Protection System
5.6 GROUPED ELEMENTS
setting. The preferred method of doing this is by
setting at the neutral of the generator and compensat-
5