Disconnect Switches - GE Multilin g60 Instruction Manual

Ur series generator protection system
Hide thumbs Also See for Multilin g60:
Table of Contents

Advertisement

5 SETTINGS

PATH: SETTINGS
SYSTEM SETUP
 SWITCH 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The disconnect switch element contains the auxiliary logic for status and serves as the interface for opening and closing of
disconnect switches from SCADA or through the front panel interface. The disconnect switch element can be used to cre-
ate an interlocking functionality. For greater security in determination of the switch pole position, both the 52/a and 52/b
auxiliary contacts are used with reporting of the discrepancy between them. The number of available disconnect switches
depends on the number of the CT/VT modules ordered with the G60.
SWITCH 1 FUNCTION: This setting enables and disables the operation of the disconnect switch element.
SWITCH 1 NAME: Assign a user-defined name (up to six characters) to the disconnect switch. This name will be used
in flash messages related to disconnect switch 1.
SWITCH 1 MODE: This setting selects "3-Pole" mode, where all disconnect switch poles are operated simultaneously,
or "1-Pole" mode where all disconnect switch poles are operated either independently or simultaneously.
GE Multilin

SWITCHES
SWITCH 1
SWITCH 1
FUNCTION: Disabled
SWITCH 1 NAME:
SW 1
SWITCH 1 MODE:
3-Pole
SWITCH 1 OPEN:
Off
SWITCH 1 BLK OPEN:
Off
SWITCH 1 CLOSE:
Off
SWITCH 1 BLK CLOSE:
Off
SWTCH 1 A/3P CLSD:
Off
SWTCH 1 A/3P OPND:
Off
SWITCH 1 B CLOSED:
Off
SWITCH 1 B OPENED:
Off
SWITCH 1 C CLOSED:
Off
SWITCH 1 C OPENED:
Off
SWITCH 1 Toperate:
0.070 s
SWITCH 1 ALARM
DELAY:
0.000 s
SWITCH 1 EVENTS:
Disabled
G60 Generator Protection System
5.4 SYSTEM SETUP

5.4.5 DISCONNECT SWITCHES

Range: Disabled, Enabled
Range: up to 6 alphanumeric characters
Range: 3-Pole, 1-Pole
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: Disabled, Enabled
5
5-79