5 SETTINGS
MESSAGE
MESSAGE
The operating characteristic is shaped out of two offset mho circles shifted down along the imaginary axis as shown below.
Figure 5–106: LOSS OF EXCITATION OPERATING CHARACTERISTICS
STAGE 1 SETTINGS:
The stage 1 characteristic is typically set to detect a loss of excitation for load conditions of 30% of the nominal or higher.
This is achieved with a mho element with a diameter equal to the base impedance of the machine and an offset equal to
half the machine transient reactance (X
The stage 1 element should be time delayed to allow for blocking by the VT fuse failure element (50 ms).
STAGE 2 SETTINGS:
The stage 2 characteristic is typically set to detect a loss of excitation for all load conditions. This is achieved with a mho
element with a diameter equal to the synchronous reactance of the machine and an offset equal to half the machine tran-
sient reactance (X
d).
During stable power swing conditions the positive-sequence impedance may momentarily enter the stage 2 characteristic.
For security of the function under such conditions, it is recommended to delay stage 2 by a minimum of 0.5 seconds.
The
setting specifies a FlexLogic™ operand for blocking the feature based on user-programmable con-
LOSS OF EXCIT BLK
ditions. When the blocking input is asserted, the element resets its timers, de-asserts the
asserted), clears self-reset targets, logs a 'blocked' event if events are enabled, and becomes inactive. When unblocked,
the element will start functioning instantly. If exposed to pickup conditions for an extended period of time and unblocked, the
element will pickup and start timing out at the moment of unblocking.
GE Multilin
LOSS OF EXCITATION
TARGET: Self-reset
LOSS OF EXCITATION
EVENTS: Disabled
X
d).
Zb
Xd
+
---------------------- - ,
CENTER 1
RADIUS 1
=
2
Xd
Xd
+
CENTER 2
---------------------- - ,
RADIUS 1
=
2
G60 Generator Protection System
5.6 GROUPED ELEMENTS
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
R
C1
= Center of element 1 = (Zb + X'd) / 2
R1
= Radius of element 1 = Zb / 2
C2
= Center of element 2 = (Xd + X'd) / 2
R2
= Radius of element 2 = Xd / 2
Zb
= Base impedance of the machine
X'd
= Transient reactance of the machine
Xd
= Synchronous reactance of the machine
830711A1.CDR
Zb
------ -
=
2
Xd
------ -
=
2
PKP
5
(EQ 5.32)
(EQ 5.33)
and
operands (if
OP
5-197