5 SETTINGS
All five triggering functions and the user-definable condition are consolidated (ORed) and connected to the PMU recorder.
Each trigger can be programmed to log its operation into the event recorder, and to signal its operation via targets. The five
triggers drive the STAT bits of the data frame to inform the destination of the synchrophasor data regarding the cause of
trigger. The following convention is adopted to drive bits 11, 3, 2, 1, and 0 of the STAT word.
SETTING
PMU 1 USER TRIGGER:
Off = 0
FLEXLOGIC OPERANDS
PMU 1 FREQ TRIGGER
PMU 1 ROCOF TRIGGER
PMU 1 VOLT TRIGGER
PMU 1 CURR TRIGGER
PMU 1 POWER TRIGGER
f) USER TRIGGERING

PATH: SETTINGS
SYSTEM SETUP
 PMU 1 USER
 TRIGGER
The user trigger allows customized triggering logic to be constructed from FlexLogic™. The entire triggering logic is
refreshed once every two power system cycles.
g) FREQUENCY TRIGGERING

PATH: SETTINGS
SYSTEM SETUP
 PMU 1 FREQUENCY
 TRIGGER
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The trigger responds to the frequency signal of the phasor measurement unit (PMU) source. The frequency is calculated
from either phase voltages, auxiliary voltage, phase currents and ground current, in this hierarchy, depending on the source
configuration as per G60 standards. This element requires the frequency is above the minimum measurable value. If the
frequency is below this value, such as when the circuit is de-energized, the trigger will drop out.
PMU 1 FREQ TRIGGER LOW-FREQ: This setting specifies the low threshold for the abnormal frequency trigger. The
comparator applies a 0.03 Hz hysteresis.
GE Multilin
bit 0
bit 1
bit 2
Figure 5–35: STAT BITS LOGIC

PHASOR MEASUREMENT...
PMU1 USER TRIGGER:
Off

PHASOR MEASUREMENT...
PMU 1 FREQ TRIGGER
FUNCTION: Disabled
PMU 1 FREQ TRIGGER
LOW-FREQ: 49.00 Hz
PMU 1 FREQ TRIGGER
HIGH-FREQ: 61.00 Hz
PMU 1 FREQ TRIGGER
PKP TIME: 0.10 s
PMU 1 FREQ TRIGGER
DPO TIME: 1.00 s
PMU 1 FREQ TRIG BLK:
Off
PMU 1 FREQ TRIGGER
TARGET: Self-Reset
PMU 1 FREQ TRIGGER
EVENTS: Disabled
G60 Generator Protection System
FLEXLOGIC OPERAND
bit 3, bit 11
PMU 1 TRIGGERED
PMU 1 recorder
847004A1.CDR


PMU 1 TRIGGERING
PMU 1 USER TRIGGER
Range: FlexLogic™ operands


PMU 1 TRIGGERING
PMU 1 FREQUENCY TRIGGER
Range: Enabled, Disabled
Range: 20.00 to 70.00 Hz in steps of 0.01
Range: 20.00 to 70.00 Hz in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: 0.00 to 600.00 s in steps of 0.01
Range: FlexLogic™ operand
Range: Self-Reset, Latched, Disabled
Range: Enabled, Disabled
5.4 SYSTEM SETUP
5
5-99