5 SETTINGS
The
setting specifies the time unit for the setting
FLEXELEMENT 1 DT UNIT
is set to "Delta". The
FLEXELEMENT 1 COMP MODE
rate of change mode of operation. This setting is applicable only if
This
FLEXELEMENT 1 PKP DELAY
specifies the reset delay of the element.

PATH: SETTINGS
FLEXLOGIC
 LATCH 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The non-volatile latches provide a permanent logical flag that is stored safely and will not reset upon reboot after the relay
is powered down. Typical applications include sustaining operator commands or permanently block relay functions, such as
Autorecloser, until a deliberate interface action resets the latch. The settings element operation is described below:
LATCH 1 TYPE: This setting characterizes Latch 1 to be Set- or Reset-dominant.
LATCH 1 SET: If asserted, the specified FlexLogic™ operands 'sets' Latch 1.
LATCH 1 RESET: If asserted, the specified FlexLogic™ operand 'resets' Latch 1.
LATCH N
LATCH N
LATCH N
TYPE
SET
RESET
Reset
ON
OFF
Dominant
OFF
OFF
ON
ON
OFF
ON
Set
ON
OFF
Dominant
ON
ON
OFF
OFF
OFF
ON
Figure 5–52: NON-VOLATILE LATCH OPERATION TABLE (N = 1 to 16) AND LOGIC
GE Multilin
FLEXELEMENT 1 DT
setting specifies the pickup delay of the element. The


NON-VOLATILE LATCHES

LATCH 1
FUNCTION: Disabled
LATCH 1 TYPE:
Reset Dominant
LATCH 1 SET:
Off
LATCH 1 RESET:
Off
LATCH 1
TARGET: Self-reset
LATCH 1
EVENTS: Disabled
LATCH N
LATCH N
ON
OFF
ON
OFF
Previous
Previous
State
State
OFF
ON
OFF
ON
ON
OFF
ON
OFF
Previous
Previous
State
State
OFF
ON
G60 Generator Protection System
FLEXELEMENT 1 dt
setting specifies duration of the time interval for the
FLEXELEMENT 1 COMP MODE
FLEXELEMENT 1 RST DELAY
5.5.8 NON-VOLATILE LATCHES
LATCH 1(16)
Range: Disabled, Enabled
Range: Reset Dominant, Set Dominant
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
SETTING
SETTING
LATCH 1 FUNCTION:
LATCH 1 TYPE:
Disabled=0
Enabled=1
RUN
SETTING
LATCH 1 SET:
Off=0
SET
SETTING
LATCH 1 SET:
Off=0
RESET
5.5 FLEXLOGIC™
. This setting is applicable only if
is set to "Delta".
setting
FLEXLOGIC OPERANDS
LATCH 1 ON
LATCH 1 OFF
842005A1.CDR