GE Multilin g60 Instruction Manual page 195

Ur series generator protection system
Hide thumbs Also See for Multilin g60:
Table of Contents

Advertisement

5 SETTINGS
The disconnect switch configuration settings are shown below. Changes to these values will not take effect until the UR is
restarted:
PATH: SETTINGS
PRODUCT SETUP
 XSWI
 CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The
setting represents the disconnect switch operating counter. As disconnect switches operate by
CLEAR XSWI1 OpCnt
opening and closing, the XSWI operating counter status attribute (OpCnt) increments with every operation. Frequent switch
operation may result in very large OpCnt values over time. This setting allows the OpCnt to be reset to "0" for XSWI1.
Since GSSE/GOOSE messages are multicast Ethernet by specification, they will not usually be forwarded by net-
work routers. However, GOOSE messages may be fowarded by routers if the router has been configured for VLAN
NOTE
functionality.
h) WEB SERVER HTTP PROTOCOL
PATH: SETTINGS
PRODUCT SETUP
 WEB SERVER
 HTTP PROTOCOL
The G60 contains an embedded web server and is capable of transferring web pages to a web browser such as Microsoft
Internet Explorer or Mozilla Firefox. This feature is available only if the G60 has the ethernet option installed. The web
pages are organized as a series of menus that can be accessed starting at the G60 "Main Menu". Web pages are available
showing DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, etc. The web pages can be
accessed by connecting the UR and a computer to an ethernet network. The main menu will be displayed in the web
browser on the computer simply by entering the IP address of the G60 into the "Address" box on the web browser.
GE Multilin


COMMUNICATIONS
IEC 61850 PROTOCOL
XSWI1 ST.LOC OPERAND
Off
XSWI2 ST.LOC OPERAND
Off
XSWI3 ST.LOC OPERAND
Off
XSWI24 ST.LOC OPERAND
Off
CLEAR XSWI1 OpCnt:
No
CLEAR XSWI2 OpCnt:
No
CLEAR XSWI3 OpCnt:
No
CLEAR XSWI24 OpCnt:
No


COMMUNICATIONS
WEB SERVER HTTP PROTOCOL
HTTP TCP PORT
NUMBER:
80
G60 Generator Protection System
5.2 PRODUCT SETUP

XSWI CONFIGURATION
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: 1 to 65535 in steps of 1
5
5-35

Advertisement