1-20 Motor Power
Range:
Size re-
*
lated
1-22 Motor Voltage
Range:
Size re-
*
lated
1-23 Motor Frequency
Option:
*
[50]
[60]
1-24 Motor Current
Range:
Size re-
*
lated
This parameter cannot be adjusted while the motor is running.
Bahasa Indonesian
Part of Language package 2
Function:
[0.12-1,600
hp
Enter the nominal motor power (in kW) according to the motor
[0.09-1,200 kW]]
nameplate data. The default value corresponds to the nominal
rated output of the unit.
This parameter cannot be adjusted while the motor is running.
This parameter is visible in LCP if par. 0-03 is
Function:
[10 - 1,000 V]
Enter the nominal motor voltage according to the motor name-
plate data. The default value corresponds to the nominal rated
output of the unit.
This parameter cannot be adjusted while the motor is running.
Function:
Min - Max motor frequency: 20 - 1,000 Hz
Select the motor frequency value from the motor nameplate
data. If a value different from 50 Hz or 60 Hz is selected, it is
necessary to adapt the load independent settings in par. 1-50
to 1-53. For 87 Hz operation with 230/400 V motors, set the
nameplate data for 230 V/50 Hz. Adapt par. 4-13
High Limit [RPM)
Hz application.
50 Hz when parame-
ter 0-03 = interna-
tional
60 Hz when parame-
ter 0-03 = US
Function:
[0.1 - 10,000 A]
Enter the nominal motor current value from the motor name-
plate data. This data is used for calculating motor torque, motor
thermal protection, etc.
MG.33.A9.22 - VLT is a registered Danfoss trademark
4. How to Program
International
and par. 3-03
Maximum Reference
[0].
4
Motor Speed
to the 87
49