6. Troubleshooting
6
The alarm words, warning words and extended status words can be read out via the serial com-
munication bus (or optional serial communication bus) for diagnosis. See also par. 16-90 - 16-94.
WARNING 1, 10 Volts low:
The 10 V voltage from terminal 50 on the con-
trol card is below 10 V.
Remove a portion of the load from terminal
50, since the 10 V supply is overloaded. Max.
15 mA or minimum 590 .
WARNING/ALARM 2, Live zero error:
The signal on terminal 53 or 54 is less than
50% of the value set in par. 6-10, 6-12, 6-20
or 6-22, respectively.
90
Alarm Word Extended Status Word
Bit
Hex
Dec
Alarm Word
0
00000001
1
Brake Check
1
00000002
2
Pwr. Card Temp ServiceTrip,
2
00000004
4
Ground Fault
3
00000008
8
Ctrl.Card Temp ServiceTrip,
4
00000010
16
Ctrl. Word TO
5
00000020
32
Overcurrent
6
00000040
64
Torque Limit
7
00000080
128
Motor Th Over
8
00000100
256
Motor ETR Over
9
00000200
512
Inverter Overld.
10
00000400
1024
DC Undervolt
11
00000800
2048
DC Overvolt
12
00001000
4096
Short Circuit
13
00002000
8192
Soft-charge
fault
14
00004000
16384
Line ph. Loss
15
00008000
32768
AMA Not OK
16
00010000
65536
Live Zero Error
17
00020000
131072
Internal Fault
18
00040000
262144
Brake Overload Fans error
19
00080000
524288
U-phase Loss
20
00100000
1048576
V-phase Loss
21
00200000
2097152
W-phase Loss
22
00400000
4194304
Ser. com. bus
fault
23
00800000
8388608
24 V Supply Low
24
01000000
16777216
Line Failure
25
02000000
33554432
1.8
V
Low
26
04000000
67108864
Brake Resistor
27
08000000
134217728
Brake IGBT
28
10000000
268435456
Option Change
29
20000000
536870912
Drive Initialized
30
40000000
1073741824 Safe Stop (A68) PTC
31
80000000
2147483648 Mech. brake low Dangerous
6.3: Description of Alarm Word, Warning Word, and extended Status Word
MG.33.A9.22 - VLT is a registered Danfoss trademark
VLT
Alarm Word 2 Warning Word
ServiceTrip,
Brake Check
Read/Write
Pwr. Card Temp
(reserved)
ServiceTrip,
Ground Fault
Typecode/
Sparepart
Ctrl.Card Temp
(reserved)
ServiceTrip,
Ctrl. Word TO
(reserved)
Overcurrent
Torque Limit
Motor Th Over
Motor ETR Over
Inverter Overld.
DC Undervolt
DC Overvolt
DC Voltage Low
DC Voltage High
Line ph. Loss
No Motor
Live Zero Error
KTY error
10 V Low
Brake Overload
ECB error
Brake Resistor
Brake IGBT
Speed Limit
Ser. com. bus fault
24 V Supply Low
Line Failure
Supply
Current Limit
Low Temp
Voltage Limit
Encoder loss
Output freq. lim.
1
Safe
Safe Stop (W68)
Stop (A71)
Extended
Status
Failure (A72)
Word
WARNING/ALARM 3, No motor:
No motor has been connected to the output of
the adjustable frequency drive.
WARNING/ALARM 4, Line power phase
loss:
A phase is missing on the supply side, or the
line voltage imbalance is too high.
This message also appears in case of a fault
in the input rectifier on the adjustable fre-
quency drive.
®
AutomationDrive FC 300 Instruction
Warning
Extended
Word 2
Status Word
Ramping
AMA Running
Start CW/CCW
Slow-down
Catch Up
Feedback High
Feedback Low
Output
Current
High
Output
Current
Low
Output Freq High
Output Freq Low
Brake Check OK
Braking Max
Braking
Out
of
Speed
Range
OVC Active
AC Brake
KTY Warn Password
Time-
lock
Fans
Password Protec-
Warn
tion
ECB Warn
Unused
Unused
Unused
Unused
Unused
Unused
Unused
Unused
PTC
1
Unused
Safe Stop
(W71)
Unused
Manual
Need help?
Do you have a question about the VLT AutomationDrive FC 300 and is the answer not in the manual?
Questions and answers