or circuit breakers can be used to provide the overcurrent protection in the installation. Overcur-
rent protection must always be carried out according to national regulations.
Fuses must be designed for protection in a circuit capable of supplying a maximum of 100,000
A
Non-UL compliance
3
If UL/cUL is not to be complied with, we recommend using the following fuses, which will ensure
compliance with EN50178:
In case of malfunction, not following the recommendation may result in unnecessary damage to
the adjustable frequency drive.
1) Max. fuses - refer to national/international regulations to select an appropriate fuse size.
28
(symmetrical), 500 V maximum.
rms
FC 300
Max. fuse size
K25-K75
1K1-2K2
3K0-3K7
5K5-7K5
11K
15K-18K5
22K
30K
37K
FC 300
Max. fuse size
K37-1K5
2K2-4K0
5K5-7K5
11K-18K
22K
30K
37K
45K
55K-75K
MG.33.A9.22 - VLT is a registered Danfoss trademark
VLT
1)
Voltage
10A
200-240 V
20A
200-240 V
32A
200-240 V
63A
380-500 V
80A
380-500 V
125A
380-500 V
160A
380-500 V
200A
380-500 V
250A
380-500 V
1)
Voltage
10A
380-500 V
20A
380-500 V
32A
380-500 V
63A
380-500 V
80A
380-500 V
100A
380-500 V
125A
380-500 V
160A
380-500 V
250A
380-500 V
®
AutomationDrive FC 300 Instruction
Type
type gG
type gG
type gG
type gG
type gG
type gG
type aR
type aR
type aR
Type
type gG
type gG
type gG
type gG
type gG
type gG
type gG
type aR
type aR
Manual