Ventilation Requirements For Gas Models - COMBITHERM CTP10-20E Installation Manual

Hide thumbs Also See for CTP10-20E:
Table of Contents

Advertisement

V E N T I L AT I O N R E Q u I R E m E N T S f O R g A S m O D E L S
W A R N I N G
To prevent SERIOUS INJURY, DEATH, or
PROPERTY DAMAGE:
Installation, air adjustment and/or service
work must be in accordance with all local
codes and must be performed by a trained
service technician qualified to work on
gas appliances.
1.
A single gas Combitherm oven requires a
minimum of 28 CFM make-up air for both natural
and propane gas. The bottom of the oven allows
necessary air flow into the appliance necessary for
gas combustion and must be kept clear at all times.
DO NOT obstruct or restrict ventilation nor
the air flow required to support combustion.
2.
It is especially critical that gas supply piping and
electrical support cord and/or receptacle be routed
away from the path of the hot combustion fumes.
3.
Make certain the oven installation maintains
adequate air ventilation to provide cooling for
electrical and gas components. The area around
the oven should be clear of any obstructions which
might retard the flow of cooling air. Failure to
observe this caution may result in damage to the
components and will void the warranty.
4.
This oven cannot be direct vented.
5.
Install the oven under a ventilation hood meeting
all applicable code requirements. Combustion
fumes must be vented in accordance with local,
state, or national codes.
N O T I C E
Inadequate ventilation, or failure to ensure an adequate air
flow may result in high ambient temperatures at the rear of
the appliance. High ambient temperatures can cause the
thermal-overload protection device on the blower motor
to trip resulting in severe damage to the blower motor.
MN-35947
Rev 12
11/16
Combitherm® CT PROformance™ and CT Classic Series Installation Manual
An adequate ventilation system is required for
commercial cooking equipment. The minimum
ventilation system shall comply with local regulations
and relevant codes. In the absence of local codes, the
ventilation system shall comply with:
USA and Canada: NFPA 96
EU: EN203
Australia/New Zealand: AS 1668.1 and AS 1668.2
The oven must be installed under a ventilation hood
listed to ANSI/UL 705 (latest edition).
WARNING
DO NOT obstruct or block exhaust flues
or attach any flue extension that may
impede proper burner operation, restrict
the exhaust fumes and cause negative
backdra or the appliance to shut down.
Failure to do so may result in serious injury
or death.
W A R N I N G
Failure to properly vent this appliance
may cause SERIOUS INJURY, DEATH, or
PROPERTY DAMAGE. The formation of
volatile substances may cause
suffocation, equipment damage,
operational problems and unsatisfactory
cooking performance as a consequence
of improper venting and is not covered
by your warranty.
Ventilation hoods and exhaust systems shall be
permitted to be used to vent appliances installed in
commercial applications.
In accordance with NFPA 54 for the
Commonwealth of Massachusetts only:
Where automatically operated appliances are
vented through a ventilation hood or exhaust
system equipped with a damper or with a power
means of exhaust, provisions shall be made to
allow the ow of gas to the main burners only
when the damper is open to a position to properly
vent the appliance and when the power means of
exhaust is in operation.
Installation
45

Advertisement

Table of Contents
loading

Related Products for COMBITHERM CTP10-20E

Table of Contents