Application Setups - Danfoss mcd-500 Operating Instruction

Soft starter
Hide thumbs Also See for mcd-500:
Table of Contents

Advertisement

MCD 500 Operating Instruction

7.3.2 Application Setups

The application setups menu makes it easy to configure the MCD 500 for common applications. The MCD 500 selects the parameters relevant to the
application and suggests a typical setting, and you can adjust each parameter to suit your exact requirements.
On the display the highlighted values are suggested values and the values indicated by a
Motor FLC
Always set par. 1-1
to match the motor's nameplate full load current. The suggested value for motor FLC is the starter's minimum FLC.
Pump Centrifugal
Motor FLC
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Stop Mode
Adaptive Stop Profile
Stop Time
Pump Submersible
Motor FLC
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Stop Mode
Adaptive Stop Profile
Stop Time
Fan Damped
Motor FLC
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Fan Undamped
Motor FLC
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
Compressor Screw
Motor FLC
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Suggested Value
Adaptive Control
Early Acceleration
5 seconds
350%
Adaptive Control
Late Deceleration
15 seconds
Adaptive Control
Early Acceleration
5 seconds
350%
Adaptive Control
Late Deceleration
5 seconds
Adaptive Control
Constant Acceleration
15 seconds
350%
Adaptive Control
Constant Acceleration
20 seconds
400%
30 seconds
20 seconds
Adaptive Control
Constant Acceleration
10 seconds
400%
MG.17.K2.02 - VLT
®
is a registered Danfoss trademark
are the loaded values.
Compressor Recip
Motor FLC
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Conveyor
Motor FLC
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Stop Mode
Adaptive Stop Profile
Stop Time
Crusher Rotary
Motor FLC
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
Crusher Jaw
Motor FLC
Start Mode
Adaptive Start Profile
Start Ramp Time
Current Limit
Excess Start Time
Locked Rotor Time
7 Programming
Suggested Value
Adaptive Control
Constant Acceleration
10 seconds
450%
Adaptive Control
Late Acceleration
15 seconds
400%
Adaptive Control
Constant Deceleration
5 seconds
Adaptive Control
Constant Acceleration
20 seconds
400%
30 seconds
20 seconds
Adaptive Control
Constant Acceleration
30 seconds
450%
40 seconds
30 seconds
7
57