Analog Output A; Start/Stop Times - Danfoss mcd-500 Operating Instruction

Soft starter
Hide thumbs Also See for mcd-500:
Table of Contents

Advertisement

7 Programming

7.8.5 Analog Output A

The MCD 500 has an analog output, which can be connected to associated equipment to monitor motor performance.
4-13 Analog Output A
Option:
Current (% FLC)*
Motor Temp (%)
Motor kW (%)
Motor kVA (%)
Motor pf
7
4-14 Analog A Scale
Option:
0-20 mA
4-20 mA*
4-15 Analog A Max Adj
Range:
100%*
[0% - 600%]
4-16 Analog A Min Adj
Range:
0%*
[0% - 600%]

7.9 Start/Stop Times

The auto-start timer overrides any other form of control. The motor may start without warning.
5-1 Auto-Start Type
Option:
Off*
Timer
Clock
5-2 Auto-Start Time
Range:
1 min*
[00:01 - 24:00 (hrs:min)]
68
Function:
Selects which information will be reported via analog output A.
Current as a percentage of motor full load current.
Motor temperature as a percentage of the motor service factor (calculated by the soft starter's
thermal model).
Motor kilowatts. 100% is motor FLC (Par. 1-1) multiplied by mains reference voltage (Par. 8-9).
Power factor is assumed to be 1.0.
V
I FLC
pf
3 ×
×
×
1000
Motor kilovolt amperes. 100% is motor FLC (Par. 1-1) multiplied by mains reference voltage (Par.
8-9).
3 ×
V
×
I FLC
1000
Motor power factor, measured by the soft starter.
Function:
Selects the range of the output.
Function:
Calibrates the upper limit of the analog output to match the signal measured on an external current
measuring device.
Function:
Calibrates the lower limit of the analog output to match the signal measured on an external current
measuring device.
Function:
Selects whether the soft starter will auto-start after a specified delay, or at a time of day.
The soft starter will not auto-start.
The soft starter will auto-start after a delay from the next stop, as specified in Par. 5-2.
The soft starter will auto-start at the time programmed in Par. 5-2.
Function:
Sets the time for the soft starter to auto-start, in 24 hour clock format.
MG.17.K2.02 - VLT
®
is a registered Danfoss trademark
MCD 500 Operating Instruction

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents