The MCD 500 is installed with a bypass contactor (AC1 rated). The bypass contactor is controlled by the MCD 500 Run Output which by default is assigned
to Output Relay B (terminals 21, 22, 24).
5
1
Control voltage (model dependent)
2
24 VDC output
3
Remote control inputs
4
Motor thermistor input (PTC only)
5
Relay outputs
6
3-phase supply
7
Motor terminals
Parameter settings:
•
Parameter 4-4
Relay B Function
•
Select Run - assigns the run output function to Relay Output B (default value).