4 Electrical Installation

4.10.6 Ferraz Fuses - AJT

Model
MCD5-0021B
MCD5-0037B
MCD5-0043B
MCD5-0053B
MCD5-0068B
MCD5-0084B
MCD5-0089B
4
MCD5-0105B
MCD5-0131B
MCD5-0141B
MCD5-0195B
MCD5-0215B
MCD5-0245C
MCD5-0360C
MCD5-0380C
MCD5-0428C
MCD5-0595C
MCD5-0619C
MCD5-0790C
MCD5-0927C
MCD5-1200C
MCD5-1410C
MCD5-1600C
30
SCR I
2
t (A
2
s)
Supply Voltage
≤ 440 VAC
1150
AJT25
8000
AJT50
10500
AJT50
15000
AJT60
15000
AJT80
512000
AJT100
80000
AJT100
125000
AJT125
125000
AJT150
320000
AJT175
320000
AJT200
320000
AJT250
320000
AJT300
238000
AJT400
320000
AJT450
320000
AJT450
1200000
A4BQ600
1200000
A4BQ800
2530000
A4BQ1200
4500000
A4BQ1200/
A4BT1100
4500000
A4BQ1600
6480000
A4BQ2000
12500000
A4BQ2500
MG.17.K2.02 - VLT
Supply Voltage
≤ 575 VAC
AJT25
AJT50
AJT50
AJT60
AJT80
AJT100
AJT100
AJT125
AJT150
AJT175
AJT200
AJT250
AJT300
AJT400
AJT450
AJT450
A4BQ600
A4BQ800
A4BQ1200
A4BQ1200
A4BT1100
A4BQ1600
A4BQ2000
A4BQ2500
®