Terminal - Danfoss VLT AQUA Drive FC 200 Operating Instructions Manual

Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

Installation
Terminal 53 default is for a speed reference signal
in open loop set in 16-61 Terminal 53 Switch
Setting
Terminal 54 default is for a feedback signal in
closed loop set in 16-63 Terminal 54 Switch Setting
Illustration 2.21 Location of Terminals 53 and 54 Switches

2.4.5.8 Terminal 37

Terminal 37 Safe Stop Function
The FC 202 is available with optional safe stop
functionality via control terminal 37. Safe stop disables the
control voltage of the power semiconductors of the
frequency converter output stage which in turn prevents
generating the voltage required to rotate the motor. When
the Safe Stop (T37) is activated, the frequency converter
issues an alarm, trips the unit, and coasts the motor to a
stop. Manual restart is required. The safe stop function can
be used for stopping the frequency converter in
emergency stop situations. In the normal operating mode
when safe stop is not required, use the frequency
converter's regular stop function instead. When automatic
restart is used – the requirements according to ISO
12100-2 paragraph 5.3.2.5 must be fulfilled.
Liability Conditions
It is the responsibility of the user to ensure personnel
installing and operating the Safe Stop function:
®
VLT
AQUA Drive
Operating Instructions
User is defined as: integrator, operator, servicing,
maintenance staff.
Standards
Use of safe stop on terminal 37 requires that the user
satisfies all provisions for safety including relevant laws,
regulations and guidelines. The optional safe stop function
complies with the following standards.
The information and instructions of the instruction manual
are not sufficient for a proper and safe use of the safe stop
functionality. The related information and instructions of
the relevant Design Guide must be followed.
Protective Measures
®
MG.20.M8.02 - VLT
is a registered Danfoss trademark
Read and understand the safety regulations
concerning health and safety/accident prevention
Understand the generic and safety guidelines
given in this description and the extended
description in the Design Guide
Have a good knowledge of the generic and safety
standards applicable to the specific application
EN 954-1: 1996 Category 3
IEC 60204-1: 2005 category 0 – uncontrolled stop
IEC 61508: 1998 SIL2
IEC 61800-5-2: 2007 – safe torque off (STO)
function
IEC 62061: 2005 SIL CL2
ISO 13849-1: 2006 Category 3 PL d
ISO 14118: 2000 (EN 1037) – prevention of
unexpected start up
Safety engineering systems may only be installed
and commissioned by qualified and skilled
personnel
The unit must be installed in an IP54 cabinet or
in an equivalent environment
The cable between terminal 37 and the external
safety device must be short circuit protected
according to ISO 13849-2 table D.4
If any external forces influence the motor axis
(e.g. suspended loads), additional measures (e.g.,
a safety holding brake) are required in order to
eliminate hazards