Applying Power To The Frequency Converter; Basic Operational Programming - Danfoss VLT AQUA Drive FC 200 Operating Instructions Manual

Hide thumbs Also See for VLT AQUA Drive FC 200:
Table of Contents

Advertisement

Start Up and Functional Tes...
3.2 Applying Power to the Frequency
Converter
WARNING
HIGH VOLTAGE!
Frequency converters contain high voltage when
connected to AC mains. Installation, start-up and
maintenance should be performed by qualified personnel
only. Failure to perform installation, start-up and
maintenance by qualified personnel could result in death
or serious injury.
WARNING
UNINTENDED START!
When frequency converter is connected to AC mains, the
motor may start at any time. The frequency converter,
motor, and any driven equipment must be in operational
readiness. Failure to be in operational readiness when the
frequency converter is connected to AC mains could result
in death, serious injury, equipment, or property damage.
1.
Confirm input voltage is balanced within 3%. If
not, correct input voltage imbalance before
proceeding. Repeat procedure after voltage
correction.
2.
Ensure optional equipment wiring, if present,
matches installation application.
3.
Ensure that all operator devices are in the OFF
position. Panel doors closed or cover mounted.
4.
Apply power to the unit. DO NOT start the
frequency converter at this time. For units with a
disconnect switch, turn to the ON position to
apply power to the frequency converter.
NOTE
If the status line at the bottom of the LCP reads AUTO
REMOTE COASTING or Alarm 60 External Interlock is
displayed, this indicates that the unit is ready to operate
but is missing an input signal on terminal 27. See
Illustration 2.22 for details.

3.3 Basic Operational Programming

Frequency converters require basic operational
programming prior to running for best performance. Basic
operational programming requires entering motor-
nameplate data for the motor being operated and the
minimum and maximum motor speeds. Enter data in
accordance with the following procedure. Parameter
settings recommended are intended for start up and
checkout purposes. Application settings may vary. See
®
VLT
AQUA Drive
Operating Instructions
4 User Interface for detailed instructions on entering data
through the LCP.
Enter data with power ON, but prior to operating the
frequency converter.
Illustration 3.1
Illustration 3.2
Illustration 3.3
®
MG.20.M8.02 - VLT
is a registered Danfoss trademark
1.
Press [Main Menu] twice on the LCP.
2.
Use the navigation keys to scroll to parameter
group 0-** Operation/Display and press [OK].
1107 RPM
Main menu
0 - ** Operation/Display
1 - ** Load/Motor
2 - ** Brakes
3 - ** Reference / Ramps
3.
Use navigation keys to scroll to parameter group
0-0* Basic Settings and press [OK].
0.0%
Operation / Display
0-0
*
Basic Settings
0-1
Set-up Opperations
*
0-2
LCP Display
*
0-3
*
LCP Custom Readout
4.
Use navigation keys to scroll to 0-03 Regional
Settings and press [OK].
0.0%
Basic Settings
0-03 Regional Settings
[0] International
5.
Use navigation keys to select International or
North America as appropriate and press [OK]. (This
changes the default settings for a number of
basic parameters. See 7 Status Messages for a
complete list.)
6.
Press [Quick Menu] on the LCP.
3.84 A