Electrical Installation

4.8.1 Control Terminal Types

Illustration 4.7 and Illustration 4.8 show the removable
frequency converter connectors. Terminal functions and
default settings are summarised in Table 4.3.
4
4
Illustration 4.7 Control Terminal Locations
Illustration 4.8 Terminal Numbers
Connector 1 provides 4 programmable digital
inputs terminals, 2 additional digital terminals
programmable as either input or output, a 24 V
DC terminal supply voltage, and a common for
optional customer supplied 24 V DC voltage.
Connector 2 terminals (+)68 and (-)69 are for an
RS-485 serial communication connection
Connector 3 provides 2 analog inputs, 1 analog
output, 10 V DC supply voltage, and commons
for the inputs and output
Connector 4 is a USB port available for use with
the MCT 10 Set-up Software
16
VLT
4
1
12 13 18 19 27 29 32 33 20 37
2
3
61 68 69
39 42 50 53 54 55
®
AQUA Drive FC 202 Operating Instructions
Terminal
12, 13
18
19
32
1
33
27
29
20
37
39
42
50
53
54
55
61
68 (+)
69 (-)
MG20MA02 - Rev. 2013-10-29
Terminal description
Default
Parameter
setting
Digital Inputs/Outputs
-
+24 V DC
24 V DC supply voltage
for digital inputs and
external transducers.
Maximum output
current 200 mA for all
24 V loads.
5-10
[8] Start
5-11
[0] No
operation
5-14
[0] No
Digital inputs.
operation
5-15
[0] No
operation
5-12
[2] Coast
For digital input or
inverse
output. Default setting
5-13
[14] JOG
is input.
-
Common for digital
inputs and 0 V
potential for 24 V
supply.
-
Safe Torque
Safe input (optional).
Off (STO)
Used for STO.
Analog Inputs/Outputs
-
Common for analog
output
6-50
Speed 0 -
Programmable analog
High Limit
output. 0-20 mA or
4-20 mA at a maximum
of 500 Ω
-
+10 V DC
10 V DC analog supply
voltage for potenti-
ometer or thermistor.
15 mA maximum
6-1
Reference
Analog input. For
voltage or current.
6-2
Feedback
Switches A53 and A54
select mA or V.
-
Common for analog
input
Serial Communication
-
Integrated RC-Filter for
cable screen. ONLY for
connecting the screen
in the event of EMC
problems.
8-3
RS-485 Interface. A
control card switch is
8-3
provided for
termination resistance.
Relays
Description