Control Terminal Programming Examples - Danfoss VLT AQUA Drive FC 202 Operating Instructions Manual

0,25-90 kw
Hide thumbs Also See for VLT AQUA Drive FC 202:
Table of Contents

Advertisement

About Frequency Converter P...
Analog Reference
6-10 Terminal 53 Low
Voltage
0.00 V
Illustration 5.4 Analog Reference 6-10 Terminal 53 Low Voltage
5.
6-11 Terminal 53 High Voltage. Set maximum
external voltage reference on Terminal 53 at 10 V.
(This sets the maximum input signal at 10 V.)
Analog Reference
6-11 Terminal 53 High
Voltage
10.00 V
Illustration 5.5 Analog Reference 6-11 Terminal 53 High Voltage
6.
6-14 Terminal 53 Low Ref./Feedb. Value. Set
minimum speed reference on Terminal 53 at 6
Hz. (This tells the frequency converter that the
minimum voltage received on Terminal 53 (0 V)
equals 6 Hz output.)
14.7 %
Analog Reference
6 - 14 Terminal 53 Low
Ref./Feedb. Value
000020.000
Illustration 5.6 Analog Reference 6-14 Terminal 53 Low Ref./Feedb.
Value
7.
6-15 Terminal 53 High Ref./Feedb. Value. Set
maximum speed reference on Terminal 53 at 60
Hz. (This tells the frequency converter that the
maximum voltage received on Terminal 53 (10 V)
equals 60 Hz output.)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
®
VLT
AQUA Drive
Operating Instructions
0.00A
Q3-21
With an external device providing a 0-10 V control signal
connected to frequency converter terminal 53, the system
is now ready for operation. Note that the scroll bar on the
right in the last illustration of the display is at the bottom,
0.00A
indicating the procedure is complete.
Q3-21
Illustration 5.8 shows the wiring connections used to
enable this set up.
0.00 A
1(1)
Q3-21
5.3 Control Terminal Programming
Control terminals can be programmed.
See Table 2.4 for control terminal parameter number and
default setting. (Default setting can change based on the
selection in 0-03 Regional Settings.)
The following example shows accessing Terminal 18 to see
the default setting.
®
MG20M902 - VLT
is a registered Danfoss trademark
14.7 %
Analog Reference
6 - 15 Terminal 53 High
Ref./Feedb. Value
50.000
Illustration 5.7 Analog Reference 6-15 Terminal 53 High Ref./
Feedb. Value
53
6-1*
U - I
A53
55
Illustration 5.8 Wiring Example for External Device Providing
0-10 V Control Signal (Frequency Converter Left, External Device
Right)
Examples
Each terminal has specified functions it is capable
of performing
Parameters associated with the terminal enable
the function
0.00 A
1(1)
Q3-21
5
+
0-10V
35
5