WAGO-I/O-SYSTEM 750
750-652 Serial Interface RS-232 / RS-485
9
Diagnostics
9.1
Serial Operating Modes
Table 43: Diagnostics, Serial Operating Modes
Diagnostics
Input buffer full The I/O module receives
Output buffer
full
Parity error
Overflow
9.2
Data Exchange Operating Mode
Table 44: Diagnostics, Data Exchange
Diagnostics
Wrong length
Checksum error Data transmission was
Timeout
Manual
Version 1.4.0
Event
data via the serial interface
faster than accepted by the
application.
The I/O module receives
data faster from the
application than it sends via
the serial interface.
Data transmission was
interrupted.
Data loss has occurred.
Event
The I/O modules have
different process image
sizes
interrupted. The last valid
value is retained in the
process image.
The data transmission is
interrupted or has been
interrupted for a longer
period of time (see
checksum error). The
process image (input) has
been overwritten with the
value 0.
Diagnostics
Solution
•
Make sure that the application
always accepts data
immediately
•
Reduce data traffic
•
Use flow control
•
Reduce baud rate
•
Check continuous send
•
Reduce data traffic
•
Increase baud rate
•
Make sure that the opposite
side accepts data
•
Check the configuration of the
interface parameters
•
Use a shielded cable
•
Change wire routing
•
Shorten cable
•
Eliminate interference
•
Reduce baud rate
Solution
•
Configure the same process
image size
•
Use a shielded cable
•
Change wire routing
•
Shorten cable
•
Eliminate interference
•
Check cable and clamping
points for uniformity
•
Check the configuration of the
I/O modules
•
for checksum error: See
Diagnostics "Checksum error"
59