Power Jumper Contacts/Field Supply; Figure 3: Power Jumper Contacts; Table 6: Legend For Figure "Power Jumper Contacts - WAGO 750-652 Manual

I/o-system 750
Hide thumbs Also See for 750-652:
Table of Contents

Advertisement

20
Device Description
3.2.2

Power Jumper Contacts/Field Supply

Risk of injury due to sharp-edged blade contacts!
The blade contacts are sharp-edged. Handle the I/O module carefully to prevent
injury.
The I/O module 750-652 has 2 self-cleaning power jumper contacts that supply
and transmit power for the field side. The contacts on the left side of the I/O
module are designed as blade contacts and those on the right side as spring
contacts.

Figure 3: Power Jumper Contacts

Table 6: Legend for Figure "Power Jumper Contacts"

Contact
1
2
3
4
Do not exceed maximum current via power jumper contacts!
The maximum current to flow through the power jumper contacts is 10 A.
Greater currents can damage the contacts.
When configuring your system, ensure that this current is not exceeded. If
exceeded, insert an additional supply module.
Type
Spring contact
Potential transmission (U
Spring contact
Potential transmission (0 V) for field supply
Blade contact
Blade contact
750-652 Serial Interface RS-232 / RS-485
Function
Potential feed-in (0 V) for field supply
Potential feed-in (U
v
WAGO-I/O-SYSTEM 750
) for field supply
v
) for field supply
Manual
Version 1.4.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-468750-468/000-001750-468/000-200750-468/025-000

Table of Contents