Setting The Rs-232 / Rs-485 Serial Interface - WAGO 750-652 Manual

I/o-system 750
Hide thumbs Also See for 750-652:
Table of Contents

Advertisement

50
Commissioning
Table 27: Parameter Range
Selection box
Switchover Time RS-485
Continuous Receive Timeout 2 Characters
*
Default setting
1)
The setting is relevant for the operating mode RS-232/RS-422, full-duplex.
2) The setting is relevant for the operating mode RS-232.
3)
The setting is relevant for the operating mode RS-485, half-duplex.
4)
Firmware version 03 or higher
Use of the CODESYS library "SerComm.lib"
Note that following settings for use of the I/O module with programmable
fieldbus controllers and use of the CODESYS library "SerComm.lib" can be
temporarily overwritten by the controller:
Mode
Baud rate
Data bits, parity, number of stop bits
Flow control
Continuous send
The following values are not available if settings should be changed by the
CODESYS library "SerComm.lib":
Mode: Data Exchange, DMX
Baud rate: 600 baud
Flow control: RTS with lead/follow-on time
8.1.5

Setting the RS-232 / RS-485 Serial Interface

Open the configuration dialog for the serial interface module. To do so, execute
the command Settings in the context menu of the I/O module (node view or
navigation).
Important note:
Before changing the parameters you should save the current values in a
parameter file. This way, in case the parameters are wrong, you can always fall
back on the original values. Use the [Save] and [Open] buttons in the parameter
dialog.
The serial I/O module is configured and prepared for communication in the
configuration area.
750-652 Serial Interface RS-232 / RS-485
Possible settings
3)
*
100 µs
/ 2 Characters / 4 Characters
*
/ 4 Characters
WAGO-I/O-SYSTEM 750
Manual
Version 1.4.0

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-468750-468/000-001750-468/000-200750-468/025-000

Table of Contents