WAGO-I/O-SYSTEM 750
750-652 Serial Interface RS-232 / RS-485
11

Appendix

11.1
Configuration and Parameterization via GSD for
PROFIBUS DP and PROFINET IO
11.1.1

Configuration of the RS-232/RS-485 Interface

11.1.1.1

PROFIBUS DP (750-333, 750-343, 750-833) Fieldbus Coupler

PROFINET IO (750-370) Fieldbus Coupler

When using the aforementioned PROFIBUS-DP and PROFINET-IO fieldbus
couplers, the process image size is configured by selecting the corresponding PI
module type.

Table 48: Configuration

PI module type
75x-652 ser. interf. 8 bytes
75x-652 ser. interf. 24 bytes
75x-652 ser. interf. 48 bytes
11.1.1.2

PROFINET IO (750-375, 750-377) Fieldbus Coupler

When using the aforementioned PROFIBUS-DP and PROFINET-IO fieldbus
couplers, the process image size is configured by selecting the corresponding
PI module / submodule type.

Table 49: Configuration

PI module
type
75x-652
serial
interface
Manual
Version 1.4.0
Represent
PI submodule
atives of
type
the
module
type
{UINT8[2],
UINT8[6]} I/O
{UINT8[2],
75x-652
UINT8[22]} I/O
{UINT8[2],
UINT8[46]} I/O
Representatives of
PI data type
the module type
Unsigned8[2]
OctetString [6]
Unsigned8[2]
75x-652
OctetString [22]
Unsigned8[2]
OctetString [46]
Process image
length
8 bytes
24 bytes
48 bytes
Appendix
Instances
Inp.
1
PI data type
Instances
Inp.
Unsigned8[2]
OctetString [6]
Unsigned8[2]
1
OctetString [22]
Unsigned8[2]
OctetString [46]
73
Outp.
1
Outp
.
1